Bug #450
SCL namespace "2007A" not accepting LDNs as "2007"
Status:
Closed
Priority:
High
Assignee:
-
Category:
Standard clarification required
Start date:
Due date:
% Done:
0%
Estimated time:
ID:
7
Source:
IOP_2013
TF Unique ID:
7 # IOP_2013
WG10 Proposal:
According to Cathedral City meeting (ref. to UFTF-CathedralMOM20160219) this issue is closed.
Estimated Completion:
WG10 June 2015 Meeting
Discuss in Upcoming Meeting:
No
To discuss in WG10:
Short Proposal:
Clarify that either- "A" is mandatory- in the case of the first revision, to supply "A" is optional
Standard(s):
IEC 61850-6
Needs More Information:
No
Assigned TF:
Description
There was an SCL file that had a Logical Device namespace (LDNs) specified as “2007”. This file did not import due to the expectation by the importer that the value would be “2007A”.
61850-6 ED.2 implies that the namespace should be “2007A”. The text reads:
“starting with A for the first released version revision”.
For clarity, the text could read: “starting with A for the first released version”.
Updated by Herbert Falk about 4 years ago
- Short Proposal changed from Clarify that either - "A" is mandatory - in the case of the first revision, to supply "A" is optional to Clarify that either- "A" is mandatory- in the case of the first revision, to supply "A" is optional
- Discuss in Upcoming Meeting set to Yes
Updated by Carlos Rodriguez del Castillo about 4 years ago
- Subject changed from There was an SCL file that had a Logical Device namespace (LDNs) specified as “2007”. This file did not import due to the expect to SCL namespace "2007A" not accepting LDNs as "2007"
- Status changed from New to Closed
- Standard(s) set to IEC 61850-6
Checking done.
I think it can be closed, but we better confirm it.
Updated by Carlos Rodriguez del Castillo almost 2 years ago
- Discuss in Upcoming Meeting changed from Yes to No
- Needs More Information set to No