Support #418
DataSets for GOOSE messaging - modeling with: only DA, only DO or both?
Status:
Closed
Priority:
Normal
Assignee:
-
Category:
Implementation - improve conformance testing
Start date:
Due date:
% Done:
0%
Estimated time:
ID:
10.1
Source:
ENTSO-E
TF Unique ID:
10.1 # ENTSO-E
WG10 Proposal:
It is already solved on Ed2 (see issue 7.1 # ENTSO-E)
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
Short Proposal:
(1) as mentioned earlier, devices should support all possible options to configure datasets. If notyet already mandatory, this should be clarified in the standard and verified with conformance testing.
Standard(s):
IEC 61850-6
Needs More Information:
Assigned TF:
Description
DataSets for GOOSE messaging - modeling with: only DA, only DO or both? Standard is not forbidding any combination (7-2, Ed.1 Member of GoCB is DataSet with MemberReference of FCD OR FCDA) but it will be implementation problem if Vendors are supporting only DA or only DO and system integrator has to decide to use one type of DataSet modeling.