Project

General

Profile

Improvement #7039

Updated by Carlos Rodriguez del Castillo 2 days ago

Standard is clear enough, a test set/simulation unit (physical or role) is the only one that can set simulation bit to true in Goose/SV frames. 
 Please take a look: 
 - IEC 61850 7-1 Ed2/2.1 section 7.8.2 figure 40 
 - IEC 61850 7-2 Ed2 sections 18.2.38 and 19.4.11 
 - IEC 61850 7-2 Ed2.1 Tables 94 and 107 

Back