CIM Issues #5076
Updated by Todd Viegut 2 months ago
Call 18 Oct 2023
Different options are possible:
-Option 1: Changing descriptions and moving attributes to SSH, or
-Option 2: In the EQ have the normal values and have another attribute (optional) in SSH
Option 2 is better option and should be implemented if there is no disagreement in Minneapolis meeting the week of 23 Oct 2023
If option 2 is approved the changes will be
Create the following attributes and add them to EQ profile in 452
GeneratingUnit.normalMaxOperatingP
GeneratingUnit.normalMinOperatingP
EquivalentInjection.normalMinP
EquivalentInjection.normalMaxP
ExternalNetworkInjection.normalMinP
ExternalNetworkInjection.normalMaxP
EquivalentInjection.normalMinQ
EquivalentInjection.normalMaxQ
ExternalNetworkInjection.normalMinQ
ExternalNetworkInjection.normalMaxQ
Add the following attributes in SSH (456), remove attributes from EQ (452) and modify the descriptions so that it is clear that SSH value depends on the operating mode
GeneratingUnit.maxOperatingP
GeneratingUnit.minOperatingP
EquivalentInjection.minP
EquivalentInjection.maxP
ExternalNetworkInjection.minP
ExternalNetworkInjection.maxP
EquivalentInjection.minQ
EquivalentInjection.maxQ
ExternalNetworkInjection.minQ
ExternalNetworkInjection.maxQ
18-Sep-2024 Joint TF Hybrid Meetings - Minneapolis:
Revisited again and reviewed. Agree to the below:
Create the following attributes which is a revision of the previous proposal. Add these to EQ profile in 452
GeneratingUnit.normalMaxEconomicP
GeneratingUnit.normalMinEconomicP
EquivalentInjection.normalMinP
EquivalentInjection.normalMaxP
ExternalNetworkInjection.normalMinP
ExternalNetworkInjection.normalMaxP
EquivalentInjection.normalMinQ
EquivalentInjection.normalMaxQ
ExternalNetworkInjection.normalMinQ
ExternalNetworkInjection.normalMaxQ
Add the following attributes in SSH (456), remove attributes from EQ (452) and modify the descriptions so that it is clear that SSH value depends on the operating mode
GeneratingUnit.maxEconomicP
GeneratingUnit.minEconomicP
EquivalentInjection.minP
EquivalentInjection.maxP
ExternalNetworkInjection.minP
ExternalNetworkInjection.maxP
EquivalentInjection.minQ
EquivalentInjection.maxQ
ExternalNetworkInjection.minQ
ExternalNetworkInjection.maxQ
Identified additional request for changes that originated from ENTSO-E. Add as part of these changes:
Rename exiting HydroPump.pumpPowerAtMaxHead to HydroPump.maxP
Rename existing HydroPump.pumpPowerAtMinHead to HydroPump.minP
The extensions in ExtHydroPump, ExtEnergyConsumer, ExtPowerElectronics and ExtGeneratingUnit need to be also moved (these were missed as they are <<NC>> extensions in the Inf* package).
We've agreed to include in CIM18v13.
The economic attributes should be in the 456 profiles.