CIM Issues #6758

Updated by Todd Viegut 2 months ago

15 May 2024 
 on item 1) the recommendation is that the measurementType should be Voltage and the association is required. 
 There is no point to have the association to the Terminal for the Switch position. 

 2) exchange of MeasurementValueSource is only for legacy implementations and new approaches are not yet supported. There are other issues open on the measurement. 

 3) 
 - Is it OK that TapPosition is analog and not discrete? yes 
 Is Discrete only boolean values or it could be also integers? No, Discrete means integer for tap position,  
 - if all is good, don't we need to add UnitSymbol.none in the Analog so that we solve the case for TapPosition which is unitless? 
 yes, we need to add it to 452 

 Follow up tasks 
 - check measurement issues 
 - fix 452 to add    UnitSymbol.none for Analog 

 16-Sep-2024 Joint TF Hybrid Meeting - Minneapolis: 
 Revisited and agreed to close out as is. Confirmed changes have been made.