[03/30/2022] WG13 agrees with the changes proposed. 


 Oslo, 13 June 2023 

 The following changes are on hold and need to be considered in the control clean up: 
 TapChanger.initialDelay to RegulatingControl.initialDelay 
 TapChanger.subsequentDelay to TapChangerControl.subsequentDelay 
 Remove ShuntCompensator.aVRDelay in favor of RegulatingControl.initialDelay 

 Note that for ctRatio and ptRatio were added to TapChanger, but these attributes are also in TapChangerInfo. Should we delete them from TapChangerInfo?  
 => The decision is that we keep it like it is so the attributes will exist on 2 places. The usege is different. 

 Question: Should ptRatio and ctRatio be added to 452 EQ? 
 =>The decision is Yes. To be decided in which profile - probably in the unbalance profile as it was needed for the distribution 

 Another question: TapChangerControl.maxLimitVoltage and minLimitVoltage are not in 452, Should we add them? 
 => We need to add them to 456 - SSH unbalanced 