CIM Issues #6202
Updated by Todd Viegut over 1 year ago
Reviewed on 12-Jun-2023 in Oslo:
Reviewed and universally agreed that this should be added to the CIM Modelling Guide document. It should be spelled out explicitly in the guide which values this should adhere to and what the required value should be. The below is what was decided should be added as a rule to the section:
Voltage (U) (e.g. voltage should be expressed using "U" e.g. not ratedkV or ratedVotage, but rather ratedU)
Active Power (P)
Reactive Power (Q)
Apparent Power (S)
Resistance (R)
Reactance (X)
Conductance (G)
Susceptance (B)
Power Factor (PF)
IMPORTANT: the rule should state that camel case is to be used. So an attribute would be just "x" and not "X" but ratedX if using camel case.
Additionally, the rule should include:
When expressing sequencing specifically for Reactance (X), (Resistance) R, Susceptance (B) and Conductance (G) the following abbreviations are to be applied:
positive -> expressed as shown above as X, R, B, G
zero sequence -> express as X0, R0, B0, G0
negative sequence -> express as X2, R2, B2, G2
NOTE: As part of this task the UML should be updated so that wherever the existing model expresses or abbreviates "Participation Factor" today as PF it should be changed to fully spell the attribute out. This will remove any ambiguity that will exist. Also we have 2 instances in the UML today where we have negative sequencing expressed as RN and XN and should be changed to R2 and X2 (this would be a breaking change). Given that CIM18 has a lot of breaking changes it is recommended this goes in at the same time (before September 2023).
Question remains as to who to assign the modeling guide updates to.
Modeling should be done by respective modeling managers where applicable.