CIM Issues #5098
Updated by Todd Viegut over 1 year ago
The description of *CsConverter.targetAlpha* currently contains the constraint: "It is only applicable for rectifier if continuous tap changer control is used."
The description of *CsConverter.targetGamma* currently contains the constraint: "It is only applicable for inverter if continuous tap changer control is used."
In the 301 we change the above respectively to:
"It is only applicable for rectifier control."
and
"It is only applicable for inverter control."
(it is also suggested that we include the below clarification on the control modes within the description in the 301 as well)
In the 456 (and 600 to reference it) we to verify and/or update if necessary:
The two control modes are mutually exclusive therefore it is expected that one, and only on, will be specified in the SSH profile (this must be verified that a constraint already exists today in the 456 for SSH that enforces this).
The SV attributes alpha and gamma for CsConverter are currently both required cardinality. They should both be optional and a constraint added to link them to the type of control declared within SSH. Only one or the other should be present but not both.