CIM Issues #5047
Updated by Chavdar Ivanov almost 2 years ago
- Added the following clarification to the EquivalentInjection description
Using EquivalentInjection to model a distribution network equivalent is recommended practice instead of using ExternalNetworkInjection-s if it is not necessary that the equivalent contains detailed information representing a short circuit equivalent according to IEC 60909 which is relevant for short circuit studies.
- Added the following clarification to the ExternalNetworkInjection description
It is only used if EquivalentInjection cannot provide the details required by IEC 60909 on short circuit equivalent of an external network.
- Deleted the folling constraint from 452
• C:452:EQ:EquivalenInjection:instance
Using EquivalentInjection to model a distribution network equivalent is recommended practice instead of using ExternalNetworkInjection-s.