Improvement #6207
Updated by Carlos Rodriguez del Castillo almost 2 years ago
Recommendation from UF:
IEC 61850-6 Amendment 2.2 to include a written statement:
- ICT shall verify the coherency of the configuration
- SCT shall maintain all Object references with valImport=true when modifying the naming scheme
- Object reference involving external referencing are strongly recommended to implement valImport=true and to allow the SCT to maintain properly the referencing.
Also ED 2.2 will provide a way of using GUID inside Object Reference Val.