Description

It is very common in distribution systems to have large single-phase motors and generators. These can be single-phase synchronous motors (e.g. reluctance motors) or asynchronous (e.g. single-phase induction motors and Type I SCIG “small-wind” turbines in the 10kW to 50kW range). CIM currently lacks any modeling detail to indicate whether a RotatingMachine is single-phase.


Files


Proposed Solution

It is proposed to add a new class named RotatingMachinePhase with minimum / essential attributes of p, q, and phase. Alternative would be two SynchronousMachinePhase and AsynchronousMachinePhase classes, but this generally not used by other classes.