IEC61850-7-5 #6832
CPOW interface with CSWI and XCBR needs to be revise.
Status:
New
Priority:
Normal
Assignee:
-
Start date:
07/25/2024
Due date:
% Done:
0%
Source:
Category:
Not yet categorized
TF 7-5 Project document:
IEC 61850-7-500
Related TISSUE:
Description
During the discussion related to phase discrepancy, we have identified that 7-500 clause 15.2 needs to be revise to explain how the exchanges are. CSWI.Pos vs CPOW.Pos - both controllable.
Is it a configuration issue, that CSWI never commands XCBR directly?
The Operate(CSWI.Pos) does not indicate with POW, so does the client control CPOW - or never.