Project

General

Profile

IEC61850-7-5 #6684

Proposal to deprecate 'LocSta' in X and Y group LN classes

Added by Michael Haecker 11 months ago.

Status:
New
Priority:
Normal
Assignee:
Manager61850-7-500
Start date:
01/22/2024
Due date:
% Done:

0%

Source:
discussion
Category:
Not yet categorized
TF 7-5 Project document:
IEC 61850-7-500
Related TISSUE:

Description

It is the purpose of 'LocSta' to define the level of control authority (remote control center vs. substation).
Since controls are to be managed by the corresponding CSWI LN instances, A-group LN instances respectively, control commands are not managed by X and Y class LN instances.

It is proposed to deprecate 'LocSta' in X and Y group LN classes.