Issues #6589
Create DataSets with Multiple Clients (for example, sDsN4)
Status:
Rejected
Priority:
Normal
Assignee:
-
Due date:
12/31/2023 (about 11 months late)
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sDsN3, sDsN4
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:
Description
When creating DataSet through multiple clients in a test that creates multiple DataSet, such as sDsN4, is each client affected by the DyDataSetMax value separately?
Or I wonder if the number of DataSet that the server can generate is the DynDataSetMax value regardless of the number of clients.
In my opinion, the number of DataSet that can be created by the server will be DynDataSetMax, but then it seems that an additional test of the process of creating Dataset through two or more clients is needed to check this.
Updated by IEC 61850 TPWG about 1 year ago
- Status changed from New to Rejected
This is the total number of dynamic datasets for the device, but there is not enough definition in the standard to add the test described.
We see no added value to the increased effort of testing with multiple clients.