Project

General

Profile

CIM Issues #6460

302, 457 issue Point of Connection

Added by Chavdar Ivanov about 1 year ago. Updated about 1 year ago.

Status:
Closed
Priority:
Normal
Author/Contact Info:
Chavdar Ivanov
Base Release:
Solution to be Applied To:
18v05
Solution Version:
CIM18v05
Solution Applied By:
Chavdar Ivanov
Completion Date:
07/01/2023
CIM Keywords:
61970-Dynamics
Breaking Change:
No
Breaking Change Description:
CIM Impacted Groups:
WG13
Requestor:
Standard(s):
Version:
Clause:
Sub-Clause:
Paragraph:
Table:
Originally Closed in Version:
Origination Date:
05/17/2023
Origination ID:
Originally Assigned To:

Description

There is a need to specify point of connection for the wind plant
the RemoteInputSignal can be used to define the point of common connection of the wind plant (park) is, using the RemoteInputSignal.Terminal reference for this purpose.
The problem is that the WindPlantDynamics.RemoteInputSignal association is of cardinality [0..1], which is not appropriate for this purpose. The cardinality should be [1..1].
The point of common connection is essential for the wind plant control model and the simulation algorithm.

This is prescribed in IEC 61400-27-1:2020


Proposed Solution

Another association could be added


Decision

Apply the proposal following IEC 61400-27-1:2020.It is prefered to add required association between WindPlantDynamics and Terminal in order not to confuse with other meaning of RemoteInputSignal.


Release Notes

The following changes are applied to 302 and 457:
- add required association WindPlantDynamics.PointOfConnection between WindPlantDynamics and Termnal

#1

Updated by Chavdar Ivanov about 1 year ago

  • Status changed from New to Open
#2

Updated by Chavdar Ivanov about 1 year ago

  • Status changed from Open to Review
#3

Updated by Chavdar Ivanov about 1 year ago

  • Status changed from Review to Closed
#4

Updated by Chavdar Ivanov about 1 year ago

  • Solution Version changed from 18v05 to CIM18v05

Also available in: Atom PDF