Issues #637
sFt4 missing expected result for step 3 and 4
Due date:
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
8-1
Triggering Tissue:
Final Decision:
Add expected result 3 and 4
Initial Test Document:
Updated Test Document:
Test Case ID:
sFt4
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:
Description
Expected result for 3 and 4 (different file) is missing. Propose expected results as follows
1. DUT sends GetFile response+
2. DUT sends GetFile response+ or response- "file busy" (PIXIT)
3. DUT sends GetFile response+
4. DUT sends GetFile response+ or response- "file busy" (PIXIT)
Updated by Richard Schimmel over 2 years ago
- Status changed from Accepted to In Progress
- Final Decision set to Add expected result 3 and 4
Updated by Richard Schimmel about 2 years ago
- Status changed from Resolved to Closed
- Initial Test Document set to Ed2Amd1 TP1.0
- Updated Test Document set to Ed2Amd1 TP1.1
- Closed Reason Test Procedure Update added