Project

General

Profile

CIM Issues #6344

[GMDM #10] Add .orderedPhases attribute on LinearShuntCompensatorPhase

Added by Pat Brown 11 months ago. Updated 11 months ago.

Status:
New
Priority:
Normal
Author/Contact Info:
Pat Brown pat@cimpledata.com
Base Release:
CIM17
Solution to be Applied To:
Solution Version:
Solution Applied By:
Completion Date:
CIM Keywords:
61970-Wires
Breaking Change:
No
Breaking Change Description:
CIM Impacted Groups:
WG13
Requestor:
Pat Brown
Standard(s):

61970-301, 61970-452, 61968-13

Version:
Clause:
Sub-Clause:
Paragraph:
Table:
Originally Closed in Version:
Origination Date:
Origination ID:
Originally Assigned To:

Description

Replace the LinearShuntCompensatorPhase.phase attribute with an .orderedPhases attribute. This allows more accurate modeling for this class as it does for other Phase classes which can be connected between wires. (As background, on TransformerTankEnd, the .phase attribute was replaced with an .orderedPhases attribute and this resolved ambiguities in open wye, open delta, and split-phase connections. And under issue GMDM 8 Redmine 6342 - Phase modeling on the low side of residential and commercial service transformers, a recommendation is made to replace the phase attribute on EnergyConsumerPhase, and PowerElectronicsConnectionPhase.)
SwitchPhase, ACLineSegmentPhase, and other “series” components wouldn’t need this change.

#1

Updated by Pat Brown 11 months ago

  • Subject changed from [GMDM #10] .orderedPhases attribute on LinearShuntCompensatorPhase to [GMDM #10] Add .orderedPhases attribute on LinearShuntCompensatorPhase
#2

Updated by Pat Brown 11 months ago

  • Base Release set to CIM17
  • Requestor set to Pat Brown

Also available in: Atom PDF