Project

General

Profile

Support #519

Optionality in DOI NamPlt, PhyNam resp. in ICD/IID file: IED.manufacturer, .IED.type, makes a device recognition in a machine to

Added by Herbert Falk almost 4 years ago. Updated over 1 year ago.

Status:
Resolved
Priority:
Normal
Assignee:
-
Category:
Profile or Guideline
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
1
Source:
UFTF
TF Unique ID:
1 # UFTF
WG10 Proposal:

To be discussed in the context of the new TF, decided to be created in Sochi, in charge of discussing IED specifications and engineering processes.(20180613)Product standard could be more strict also for SCL files. Engineering guideline could also address the issue (system management TF?).

Estimated Completion:
2019 (first draft)Draft is not still available. Contact Thierry Coste and Laurent Guise
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:

Ask Thierry for clarifications and for completion on following proposals.1. If this request is for offline use only, then specify that manufacturer and type value appears in the ICD file. 2. If this request if for online use, then add restriction that valKind shall not be conf on this attributes.

Standard(s):

80-7

Needs More Information:
No
Assigned TF:

Description

Optionality in DOI NamPlt, PhyNam resp. in ICD/IID file: IED.manufacturer, .IED.type, makes a device recognition in a machine to machine environment almost impossible.
Product standard could be more strict also for SCL files. Engineering guideline could also address the issue (system management TF?).

#1

Updated by Carlos Rodriguez del Castillo over 2 years ago

  • Status changed from New to Resolved
  • WG10 Proposal changed from To be discussed in the context of the new TF, decided to be created in Sochi, in charge of discussing IED specifications and engineering processes. (20180613) Product standard could be more strict also for SCL files. Engineering guideline could also address the issue (system management TF?). to To be discussed in the context of the new TF, decided to be created in Sochi, in charge of discussing IED specifications and engineering processes.(20180613)Product standard could be more strict also for SCL files. Engineering guideline could also address the issue (system management TF?).
  • Estimated Completion changed from 2019 (first draft) Draft is not still available. Contact Thierry Coste and Laurent Guise to 2019 (first draft)Draft is not still available. Contact Thierry Coste and Laurent Guise
  • Discuss in Upcoming Meeting set to No
  • To discuss in WG10 set to No
  • Short Proposal changed from Ask Thierry for clarifications and for completion on following proposals. 1. If this request is for offline use only, then specify that manufacturer and type value appears in the ICD file. 2. If this request if for online use, then add restriction that valKind shall not be conf on this attributes. to Ask Thierry for clarifications and for completion on following proposals.1. If this request is for offline use only, then specify that manufacturer and type value appears in the ICD file. 2. If this request if for online use, then add restriction that valKind shall not be conf on this attributes.

Check before end of year 2022.

#2

Updated by Carlos Rodriguez del Castillo over 1 year ago

  • Discuss in Upcoming Meeting changed from No to Yes
  • Standard(s) changed from 90-16 to 80-7
  • Needs More Information set to No

The request is probably to change the presence condition from O to M for these data objects and also to be present at SCL.
90-16 described use cases, 80-7 is the specification document.
We have to follow it. Contact 80-7 TF leader.

#3

Updated by Carlos Rodriguez del Castillo over 1 year ago

  • Discuss in Upcoming Meeting changed from Yes to No

Also available in: Atom PDF