Add 61869-9 sample rates to UCA conformance certificates?

Added by Bruce Muschlitz almost 3 years ago. Updated over 2 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Due date:
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:

Description

Redmine database has the capability to record the nominal frequencies, sampling rates, and variants (without dataset declared).
However, Ed2.1 Certificates do not include this information (it was included on the 9-2LE (Ed1 publisher) certificates.
Suggest to add that information to the certificate.
Information frequency is limited to DC or 50Hz or 60Hz.
Information on variants can be selected from:
9-2LE (legacy) rates: F4000S1, F4800S1, F5760S1, F12800S8, F15360S8
preferred rates: F4800S2, F14400S6, F96000S1

Note that 61869-9 conformance test requires that each unique rate/nofASDU combination be individually tested (it allows a single data set to be chosen for each rate regardless of the number of analog channels available for that rate/nofASDU)


Related issues

Related to Server - Issues #5308: SV Publisher/subscriber maximum dataset size is untestedClosedActions
#1

Updated by Herbert Falk over 2 years ago

  • Related to Issues #5308: SV Publisher/subscriber maximum dataset size is untested added
#2

Updated by Bruce Muschlitz over 2 years ago

  • Status changed from New to Closed
  • Discuss in Upcoming Meeting changed from Yes to No
  • Updated Test Document set to Server Ed2.1 TP1.2
  • Closed Reason Test Procedure Update added
  • Closed Reason deleted (--Not Set---)

See R5293 and R5308 for resolutions