CIM Issues #5048
Better descriptions for HVDC model
Description
Per CDV country comments CH_71, NO64 & SE68 for 301 Ed7:
HVDC model needs more explanations and examples.
Proposed Solution
Add the proposal presented in Annex 1 (Proposed modifications related to HVDC) in 61970-301.
WG 13 - The sequenceNumber attribute is used the same for DC as it is for AC.
WG 13 (Oct. 23) - Agreed that ACDCTerminal.sequenceNumber is used the same for AC and DC. The description does not need to be changed. (NOTE: Discovered that all the below attributes were already modified in CIM17 prior to CIM18)
Agreed to add the sentence "The attribute shall be a positive value." to the following attributes:
ACDCConverter - maxUdc, minUdc, targetUdc, uc, & udc
CsConverter - maxIdc, minIdc, targetIdc
VsConverter - targetUpcc.
Review below with WG13:
Per country comments:
"Specify if target values are all positive values or can be negative or zero. Specify sign conventions. For targetUdc it is suggested to restrict to only positive values and for CsConverter to rely on CsConverter.operatingMode (inverter/rectifier) which would define the sign of Udc. ================================================================
Specify the relation between ACDCConverter.p, .q and the target values on active power, voltage, reactive power."
WG13 agreed that changes to the descriptions of targetUdc and the other target values should be added once the relationships between the detailed attributes has been further clarified.
Final proposal includes applying HVDC modifications as described in Chavdar's proposal (See email from Dec. 9th, 2019).
Decision
14-Jan-2020 Decision to apply the proposed resolution when revving to CIM18
Updated by Yang Feng about 2 years ago
- Subject changed from Per CDV country comments CH_71, NO64 & SE68 for 301 Ed7: H to Per CDV country comments CH_71, NO64 & SE68 for 301 Ed7:H
- Proposed Solution updated (diff)
Updated by Yang Feng over 1 year ago
- Subject changed from Per CDV country comments CH_71, NO64 & SE68 for 301 Ed7:H to Better descriptions for HVDC model
Updated by Chavdar Ivanov about 1 year ago
- Status changed from Open to In Progress
I am closing the issues as the changes are already imlemented in CIM17. The relation between the target valies and the types of control is also in the model in the respective enumerations.