CIM Issues #4985
Description of PetersenCoil.xGroundNominalxGroundNominal c
Status:
Closed
Priority:
Normal
Author/Contact Info:
Svein Olsen Statnett
Base Release:
61970cim17v06
Solution to be Applied To:
Solution Version:
Solution Applied By:
Completion Date:
CIM Keywords:
Breaking Change:
No
Breaking Change Description:
CIM Impacted Groups:
WG13
Requestor:
Standard(s):
Version:
Clause:
Sub-Clause:
Paragraph:
Table:
Originally Closed in Version:
Origination Date:
03/11/2015
Origination ID:
13_239
Originally Assigned To:
Description
Description of PetersenCoil.xGroundNominal
xGroundNominal calculation in the attribute description is incorrect. Impedance is nominal Voltage divided by the set point in Amps. The position current is a secondary control input, and should not be mixed with the "primary" current that is a function of this control current. A new attribute may be required, either for scaling position current or as the primary set point in Amps. The latter is clearly to be preferred from a planning model perspective.
Decision
Legacy issue resolved in CIM17. Issue is moved to closed.
Updated by Eric Stephan over 1 year ago
- Subject changed from Description of PetersenCoil.xGroundNominal xGroundNominal c to Description of PetersenCoil.xGroundNominalxGroundNominal c
- Status changed from Open to Review
- Decision updated (diff)