Project

General

Profile

CIM Issues #4065

StaticLoadType enumeration and properties on LoadStatic pro

Added by Herbert Falk over 2 years ago.

Status:
Closed
Priority:
Normal
Author/Contact Info:
Kendall Demaree
Base Release:
61970cim15v26
Solution to be Applied To:
61970cim16
Solution Version:
CIM16
Solution Applied By:
LOO
Completion Date:
01/17/2013
CIM Keywords:
Breaking Change:
No
Breaking Change Description:
CIM Impacted Groups:
WG13
Requestor:
Standard(s):
Version:
Clause:
Sub-Clause:
Paragraph:
Table:
Originally Closed in Version:
CIM16
Origination Date:
06/30/2011
Origination ID:
13_73
Originally Assigned To:

Description

StaticLoadType enumeration and properties on LoadStatic probably duplicate LoadResponseCharacteristic
This seems very similar if not identical idea as specified on LoadResponceCharacterisitc class. The details are not documented on the enum values or the attributes, so its hard to tell exactly.


Proposed Solution

Probably can delete many attributes of StaticLoad class and delete the whole of enumeration StaticLoadType. Would add association LoadStatic[0..*]-LoadResponseCharacterisitc[0..1]. This is similar to how an EnergyConsumer uses LoadResponseCharacteristic. LoadStatic is not a ConductingEquipment, so cannot specialize EnergyConsumer to obtain the association. There may be other properties of EnergyConsumer that we want consistent with LoadStatic though.


Decision

StaticLoadType and LoadStatic not in CIM.
Agreed to close WG13 meet no 106
2013-01-17: LOO