Project

General

Profile

CIM Issues #6452

Updated by Chavdar Ivanov about 1 month ago

Applied changes in canonical CIM 
 - added class StepOperationalLimitTable 
 - added class StepLimitTablePoint with attributes step and factor 
 - the association end RatioTapChanger.TransformerEnd is changed from 1 to 0..1 
 - new association is added between RatioTapChanger and TransformerEnd 
 - added class ConnectionAngleTapChangerTable with attribute ConnectionAngleTapChangerTable.windingConnectionAngle  
 - added class ConnectionAngleTapChanger 
 - added ConnectionAngleTapChanger.minWindingConnectionAngle, maxWindingConnectionAngle, connectionAngleStepSize, windingConnectionAngle, normalWindingConnectionAngle 

 - added class ImpedanceTapChangerTabular 
 - added class ImpedanceTapChangerTable 
 - added class ImpedanceTapChangerTablePoint with the following attributes: xEnd1, xEnd2, xEnd3, rEnd1, rEnd2, rEnd3, step, ratio, angle. 
 - the text "Note that the upper boundary is not constrained to 100 percent." is added to TapChangerTablePoint.b, .g, .r, .x 

 Changes are also applied to EQ (452) and SSH profiles (456)