CIM Issues #5946
Updated by Chavdar Ivanov almost 2 years ago
The following changes are applied:
in the Topology profile (to be published in 61970-456)
- remove association Terminal.TopologicalNode
- remove association DCBaseTerminal.DCTopologicalNode (note the association DCNode to DCTopologicalNode is already required association)
- delete classes Terminal, ACDCTerminal, DCBaseTerminal, ACDCConverterDCTerminal, DCTerminal as they are no longer needed in the profile after removal of the associations.
in the Equipment profile (to be published in 61970-452)
- change cardinality of association Terminal.ConnectivityNode from 0..1 to 1. This is necessary bacause since CIM17 the models are build on the basis of ConnectivityNode for both node breaker and bus branch modelling styles.
- change the cardinality of the DCBaseTerminal.DCNode from 0..1 to 1. This will match the way it is done for AC part.
- the following rule was updated
R:452:ALL:ConductingEquipment:connectivity
All subtypes of ConductingEquipment are required to have associations to Terminals. The number of associated Terminals is specified in IEC 61970-301 in section 4.8.2 “Number of terminals for ConductingEquipment objects.”