Bug #6263

Updated by Abhilash Appukuttan almost 2 years ago

In Part 6, the MinTime and MaxTime is expressed as 'Decimal' 'Integer'  

 <xs:complexType name="tGSE"> 
 <xs:complexContent> 
 <xs:extension base="tControlBlock"> 
 <xs:sequence> 
 <xs:element name="MinTime" type="tDurationInMilliSec" minOccurs="0"/> 
 <xs:element name="MaxTime" type="tDurationInMilliSec" minOccurs="0"/> 
 </xs:sequence> 
 </xs:extension> 
 </xs:complexContent> 
 </xs:complexType> 
 --- 
 <xs:complexType name="tDurationInMilliSec"> 
 <xs:simpleContent> 
 <xs:extension base="xs:decimal"> 
 <xs:attribute name="unit" type="tSIUnitEnum" use="optional" fixed="s"/> 
 <xs:attribute name="multiplier" type="tUnitMultiplierEnum" use="optional" fixed="m"/> 
 </xs:extension> 
 </xs:simpleContent> 
 </xs:complexType> 

 However, in 8-1, the MinTime and MaxTime is an Unsigned32 / INT32U 

 MinTime Unsigned32 r o INT32U – As specified in the SCD 
 file for the GoCB, See 1 
 MaxTime Unsigned32 r o INT32U – As specified in the SCD 
 file for the GoCB. See 1 

 What shall the ICT process the values as? Input as Decimal and then pass it as Integer to the application? 

 Or does it makes sense to change the -6 to have these values as Integer? 

 If you look at Table 45 in -6, it does point to that way.  



 INT8, INT16, INT24, INT32, 
 INT64 
 INT8U, INT16U, INT32U 

 integer  

 An integer number, no decimal fraction (99999) 