 NonlinearShuntCompensatorPoint should be aligned with NonlinearShuntCompensator. 
 Proposed change to the NonlinearShuntCompensatorPoint: 
 -b- bTotal: -Positive sequence shunt (charging) susceptance per section.- Total positive sequence shunt (charging) susceptance at section noted by sectionNumber. Inductive is negative value, capacitive is positive value. 
 -b0- b0Total: -Zero sequence shunt (charging) susceptance per section.- Total zero sequence shunt (charging) susceptance at section noted by sectionNumber. Inductive is negative value, capacitive is positive value. 
 -g- gTotal: -Positive sequence shunt (charging) conductance per section.- Total positive sequence shunt (charging) conductance at section noted by sectionNumber. Conductance must be positive value. 
 -g0- g0Total: -Zero sequence shunt (charging) conductance per section.- Total zero sequence shunt (charging) conductance at section noted by sectionNumber. Conductance must be positive value. 