NonlinearShuntCompensatorPoint should be aligned with NonlinearShuntCompensator.
Proposed change to the NonlinearShuntCompensatorPoint:
b: -Positive sequence shunt (charging) susceptance per section.- Total positive sequence shunt (charging) susceptance at section noted by sectionNumber. Inductive is positive value, capacitive is negative value.
b0: -Zero sequence shunt (charging) susceptance per section.- Total zero sequence shunt (charging) susceptance at section noted by sectionNumber.
g: -Positive sequence shunt (charging) conductance per section.- Total positive sequence shunt (charging) conductance at section noted by sectionNumber.
g0: -Zero sequence shunt (charging) conductance per section.- Total zero sequence shunt (charging) conductance at section noted by sectionNumber.