Project

General

Profile

Issues

Filters

Apply Clear

# Project Tracker ID Source Status Priority Standard(s) Subject Updated
6226 IEC 61850 User Feedback Task Force Bug Resolved Normal In the downgrading rules from ed 2.1 to ed 2.0 in part 6, it is mentionned to exclude ORS CDC (I.4.2.4). Why CDCs: CST, VSD and TCS that were also added in ed2.1 are not mentionned to be excluded also ? 01/17/2023 08:58 AM Actions
6175 IEC 61850 User Feedback Task Force Bug 2022 IOP In Progress Normal

IEC 61850-6

SCL SICS requires SNTP even with 2.1 where PTP is the preferred method. 11/08/2022 08:18 AM Actions
442 IEC 61850 User Feedback Task Force Bug 5 Vattenfall Resolved High

IEC 61850-6-100

Maping LNode (substation section) to LN (IED section) 03/15/2022 09:10 AM Actions
3101 IEC 61850 User Feedback Task Force Bug 3 TissueDB Resolved Normal

IEC 61850-7-4

IEC61850.Tissue #1755 Event driven schedules – Add DO to stop schedule by event 11/23/2021 08:34 AM Actions
611 IEC 61850 User Feedback Task Force Bug 5 RTE In Progress Normal

IEC 61850-7-4 / IEC 61850-80-6

Need a new DO (ENUM) to identify the protocol used for the SCADA exchange, in LN ITCI 05/11/2021 09:59 AM Actions
439 IEC 61850 User Feedback Task Force Bug 2 Vattenfall In Progress High

IEC 61850-6

How to add utility process name to DOs 02/11/2021 06:37 AM Actions
5077 IEC 61850 User Feedback Task Force Feature 1 MH Resolved Normal

IEC61850 7-1

Location of SGCB in LD structures 02/02/2023 08:16 AM Actions
6246 IEC 61850 User Feedback Task Force Feature New Normal ExtRef cannot specify a Poll intended to be implemented as a GetDataSetValues request  02/02/2023 07:04 AM Actions
6216 IEC 61850 User Feedback Task Force Feature 51 RTE New Normal

IEC 61850-7-4

Parameters not available in standardized LN - SetPhNum 01/16/2023 09:20 AM Actions
6225 IEC 61850 User Feedback Task Force Feature 60 RTE New Normal

IEC 61850-7-4

Parameters not available in standardized LN - SetPhsOrig 01/16/2023 09:19 AM Actions
6222 IEC 61850 User Feedback Task Force Feature 57 RTE New Normal

IEC 61850-7-4

Parameters not available in standardized GAPC LN - SetNb 01/16/2023 09:18 AM Actions
6224 IEC 61850 User Feedback Task Force Feature 59 RTE New Normal

IEC 61850-7-4

Parameters not available in standardized GAPC LN - SetRef 01/16/2023 09:17 AM Actions
6223 IEC 61850 User Feedback Task Force Feature 58 RTE New Normal

IEC 61850-7-4

Parameters not available in standardized GAPC LN - StrVal 01/16/2023 09:15 AM Actions
6221 IEC 61850 User Feedback Task Force Feature 56 RTE New Normal

IEC 61850-7-4

Parameters not available in standardized GAPC LN - OnOff 01/16/2023 09:14 AM Actions
6219 IEC 61850 User Feedback Task Force Feature 54 RTE New Normal

IEC 61850-7-4

Parameters not available in standardized LN - VRtg, ARtg and HzRtg 01/16/2023 09:07 AM Actions
6218 IEC 61850 User Feedback Task Force Feature 53 RTE New Normal

IEC 61850-7-4

Parameters not available in standardized LN - PhyConnITF 01/16/2023 09:06 AM Actions
6217 IEC 61850 User Feedback Task Force Feature 52 RTE New Normal

IEC 61850-7-4

Parameters not available in standardized LN - NamAccRtg 01/16/2023 09:06 AM Actions
5374 IEC 61850 User Feedback Task Force Feature RTE In Progress Normal

IEC 61850-7-4

Creation of a new LN for protection function 12/20/2022 08:57 AM Actions
597 IEC 61850 User Feedback Task Force Feature 1120 IOP_2019 Resolved Normal

TF Communication supervision

SCTs updating the confRev of 9-2 LE Sampled Value streams - problem with subscription to test tool SV injection 09/26/2022 09:55 AM Actions
602 IEC 61850 User Feedback Task Force Feature 1742 IOP_2019 Resolved Normal

IEC 61850-9-3

Merging Unit standard requires MU clock to jump on PTP time jumps, which is not true for Boundary Clocks. 07/05/2022 08:52 AM Actions
599 IEC 61850 User Feedback Task Force Feature 12 IOP_2019 Resolved Normal ICD files do not match requirements (several issues) - increase in engineering efforts 07/05/2022 08:48 AM Actions
590 IEC 61850 User Feedback Task Force Feature 1800 IOP_2019 In Progress Normal

IEC 61850-6

ICT fails to check validity of the SCD file regarding the IED constraints 07/05/2022 08:30 AM Actions
584 IEC 61850 User Feedback Task Force Feature 1122 IOP_2019 Resolved Normal

IEC 61850-6

SCL validation - Should all name parts of PhV be contained in the doName? 07/05/2022 08:20 AM Actions
612 IEC 61850 User Feedback Task Force Feature 11 RTE Resolved Normal

IEC 61850-7-4

Need to create a new LN of group P (Protection), as "PCDP" to represent the Pole Discrepancy Protection. 07/05/2022 08:17 AM Actions
5123 IEC 61850 User Feedback Task Force Feature 2 TF 61850-80-6 Resolved Normal

IEC 61850-90-28

ACSI service for link supervision on application level 06/21/2022 08:35 AM Actions
(1-25/1897) Per page: 25, 50, 100

Also available in: Atom CSV PDF