# Project Tracker ID Source Status Priority Standard(s) Subject Updated
495 IEC 61850 User Feedback Task Force Support 10 IOP_2015 Closed Normal

6

Issue 2: SCT Behavior When Revising/Replacing IED Configuration Between SCT Tools In terms of the data model structure and comm 06/21/2022 09:12 AM Actions
418 IEC 61850 User Feedback Task Force Support 10.1 ENTSO-E Closed Normal

IEC 61850-6

DataSets for GOOSE messaging - modeling with: only DA, only DO or both? 02/11/2021 08:02 AM Actions
419 IEC 61850 User Feedback Task Force Support 10.2 ENTSO-E Closed Normal

IEC 61850-7-2

Also many other features of GOOSE messaging are left to the manufacturer to choose. 12/06/2022 09:01 AM Actions
454 IEC 61850 User Feedback Task Force Bug 11 IOP_2013 Closed High Data model: extension of logical nodes with new DOs. Question about namespace. 02/09/2021 06:16 AM Actions
420 IEC 61850 User Feedback Task Force Support 11 ENTSO-E Closed Normal Procedures to establish client / server communications should be defined 06/05/2023 01:59 AM Actions
530 IEC 61850 User Feedback Task Force Feature 11 IOP_2017/20 Closed Normal

IEC 61850-6

SCT is passing ICD errors to SCD. 06/21/2022 09:24 AM Actions
496 IEC 61850 User Feedback Task Force Support 11 IOP_2015 Closed Normal

6

DUSTIN: Issue 3: Symmetrical Bindings of DA In case of late Binding at DO/DA Level. IED expects DO at later binding, but source 06/21/2022 09:12 AM Actions
597 IEC 61850 User Feedback Task Force Feature 1120 IOP_2019 Resolved Normal

61850-90-28

SCTs updating the confRev of 9-2 LE Sampled Value streams - problem with subscription to test tool SV injection 05/09/2023 09:32 AM Actions
584 IEC 61850 User Feedback Task Force Feature 1122 IOP_2019 Closed Normal

IEC 61850-6

SCL validation - Should all name parts of PhV be contained in the doName? 05/09/2023 09:12 AM Actions
421 IEC 61850 User Feedback Task Force Support 12 ENTSO-E Closed Normal

IEC 61850-4

Project management as proposed by IEC61850-4 is not supported by commercially available tools 06/05/2023 01:59 AM Actions
599 IEC 61850 User Feedback Task Force Feature 12 IOP_2019 Resolved Normal ICD files do not match requirements (several issues) - increase in engineering efforts 06/05/2023 01:58 AM Actions
531 IEC 61850 User Feedback Task Force Feature 12 IOP_2017/21 Closed Normal

IEC 61850-8-1, IEC 61850-9-2

Merging Unit is not capable to publish SV outside of the recommended destination MAC address range (even though 8-1 is informative) 06/21/2022 09:24 AM Actions
497 IEC 61850 User Feedback Task Force Support 12 IOP_2015 Closed Normal

6

Issue 2 - IED restrictions not known by SCT 2.1 IED support 50% URCB and 50% BRCB Service section provide a total RCB number 2. 06/21/2022 09:12 AM Actions
455 IEC 61850 User Feedback Task Force Feature 12 IOP_2013 Closed Normal How does a SCT know the maximum number of instantiated RCBs allowed in an IED and what the allowed distribution per RCB? 02/11/2021 07:47 AM Actions
422 IEC 61850 User Feedback Task Force Support 13 ENTSO-E Closed Normal Mapping utility signals to IEC 61850 objectcs from specification perspective 06/05/2023 01:59 AM Actions
532 IEC 61850 User Feedback Task Force Feature 13 IOP_2017/22 Closed Normal

IEC 61850-7-2

An implementation do not allow BRCB resvTms to be written while rptEnable is True 06/21/2022 09:24 AM Actions
498 IEC 61850 User Feedback Task Force Support 13 IOP_2015 Closed Normal

6

Issue 3 – GoCB confRev - behaviour if ConfRev=“0“ IED rejected that value. 7-2: If there are inconsistent attribute values in t 06/21/2022 09:12 AM Actions
456 IEC 61850 User Feedback Task Force Support 13 IOP_2013 Closed Normal A client only ICD did not have a ClientServices section. An SCT imported the file and assigned used the IED to reserve a RCB wit 06/21/2022 09:00 AM Actions
585 IEC 61850 User Feedback Task Force Feature 1337 IOP_2019 Closed Normal

IEC 61850-6

SCT unable to configure the device to communicate on multiple subnets due to having a single AP (with all Eth. Ports) 07/05/2022 08:24 AM Actions
586 IEC 61850 User Feedback Task Force Feature 1340 IOP_2019 Closed Normal

IEC 61850-6

Client application cannot connect to IED that are having issue with format of AP-Title 07/05/2022 08:26 AM Actions
533 IEC 61850 User Feedback Task Force Support 14 IOP_2017/23 Closed Normal MSVID shall be unique. The integrated application SCD file allowed duplicate SVID’s for two merging units. 06/21/2022 09:13 AM Actions
499 IEC 61850 User Feedback Task Force Support 14 IOP_2015 Closed Normal

6

Issue 4 – Private section – namespace moved from SCL node to Private nodes ICT added the namespace within the privates instead o 06/21/2022 09:12 AM Actions
423 IEC 61850 User Feedback Task Force Support 14 ENTSO-E Closed Normal Conformance test for SICS. 02/11/2021 07:47 AM Actions
457 IEC 61850 User Feedback Task Force Feature 14 IOP_2013 Closed Normal

IEC 61850-6

A SCL file is created without maxAttributes attribute defined. What does it mean semantically it the attr. is missing? 02/11/2021 07:46 AM Actions
587 IEC 61850 User Feedback Task Force Feature 1404 IOP_2019 Closed Normal

IEC 61850-6

LNodeTypes and DOTypes not used in the IED section - is it allowed to keep them in DataTypeTemplate section? 02/11/2021 07:01 AM Actions