Incorrect signal direction for GOOSE messages between CSWI and XCBR
0%
Description
From the TISSUE:
Issue
In IEC 61850-7-500:2017, Table 4 shows the extension of the control model by GOOSE messages between CSWI and XCBR. The direction of the arrows on the last two rows is incorrect.
Proposal
The GOOSE message direction should be going FROM CSWI.SelOpn/Cls.stVal TO the XCBR, and not the other way around. And the GOOSE message direction should be going FROM XCBR.Pos.stSeld TO CSWI.Pos.stSeld, and not the other way around. The direction of the flow of GOOSE messages is correctly depicted in Figures 21 and 22 that are associated with Table 4.
Updated by Keith Gray 11 months ago
- TF 7-5 Project document IEC 61850-7-500 added
- TF 7-5 Project document deleted (
-)
Updated by Keith Gray 11 months ago
- Status changed from New to In Progress
- Assignee set to Keith Gray
During the 2024/02 WG10 meeting, we revised the table to correct the arrow directions. Michael has created a document containing only the snippet of this table for later inclusion in the updated 7-500 document. This snippet document is on the collaboration platform.
Updated by Keith Gray 10 months ago
I have updated the document in preparation for the 2024/02/29 TF meeting.
Updated by Keith Gray 10 months ago
- Status changed from In Progress to Waiting for Release
Reviewed during the 2024/02/29 TF meeting.