Project

General

Profile

IEC 61850 Certificate #6660

PSF640 Feeder Protection and Control

Added by Herbert Falk 4 months ago. Updated 4 months ago.

Status:
Approved
Priority:
Normal
61850 Edition:
Edition 2
61850 Tested Aspects:
Server
Company:
"GUODIAN NANJING AUTOMATION CO., LTD. /NANJING SAC POWER GRID AUTOMATION CO., LTD."
Address:

No.39, Shuige Road, Jiangning Development Zone, 211153, Nanjing, PEOPLE'S REPUBLIC OF CHINA

Product:
PSF640 Feeder Protection and Control
HW Version:
V1.00
SW Version:
V1.0.0
Key Words:
Feeder, Protection
Test Procedure Version:

2.0.6

IEC 61850 Blocks Certified:
Basic Exchange (B1), Buffered Reporting (B6), Data Sets (B2), Direct Control (12a), Enhanced SBO Control (12d), File Transfer (B14), GOOSE Publish (9a), GOOSE Subscribe (9b), Setting Group (B4), Setting Group Definition (B4+), Time Synchronization (B13), Unbuffered Reporting (B5)
Certificate/Result Reviewer:
Herbert Falk
Approval Date:
12/28/2023
Standards Tested:
61850-6, 61850-7-1, 61850-7-2, 61850-7-3, 61850-7-4, 61850-8-1
Current Test Lab Name:
TUV SUD China Ltd (A)
Certificate Name:
23-D 002427 0011_SAC_PSF640_IEC61850Ed2.0_Server_Certificate.pdf
Certificate Hash:
SHA256: 28F16B46EB272EE240FE8363C92788FFD3FA56A90D3F6DBBBBE16A03F6F3890A
Vendor Artifact File Name:
Vendor Artifact Hash:
Umbrella Organization:
Optional Reservation Test:
Yes
Serial Number:
Publisher Legacy Variants:
-
Publisher Preferred Rates:
-
Publisher Preferred Variants:
Subscriber Legacy Variants:
-
Subscriber Preferred Variants:
Subscriber Preferred Rates:
-

Description

PSF640 is a dedicated feeder protection and control IED, perfectly aligned for protection, control, measurement, and supervision in isolated neutral, resistance grounded or compensation grounded utility substations and industrial power distribution systems with 66kV and below voltage level.


Files

#1

Updated by Herbert Falk 4 months ago

  • IEC 61850 Blocks Certified Buffered Reporting (B6), Data Sets (B2), Direct Control (12a), Enhanced SBO Control (12d), File Transfer (B14), GOOSE Publish (9a), GOOSE Subscribe (9b), Setting Group (B4), Setting Group Definition (B4+), Time Synchronization (B13), Unbuffered Reporting (B5) added
#2

Updated by Herbert Falk 4 months ago

  • Optional Reservation Test changed from No to Yes

Also available in: Atom PDF