Project

General

Profile

CIM Issues #6457

302, 457 issue WindPlantQControlIEC

Added by Chavdar Ivanov 11 months ago. Updated 11 months ago.

Status:
Closed
Priority:
Normal
Author/Contact Info:
Chavdar Ivanov
Base Release:
Solution to be Applied To:
18v05
Solution Version:
CIM18v05
Solution Applied By:
Chavdar Ivanov
Completion Date:
07/01/2023
CIM Keywords:
Breaking Change:
No
Breaking Change Description:
CIM Impacted Groups:
WG13
Requestor:
Standard(s):
Version:
Clause:
Sub-Clause:
Paragraph:
Table:
Originally Closed in Version:
Origination Date:
Origination ID:
Originally Assigned To:

Description

the class WindPlantQControlIEC has 2 attributes qwpmin and qwpmax. IEC 61400-27-1:2020, 7.9.2.
defines them as a function of Pwp. Therefore it is not correct that these are attributes, they need to be lookup table


Proposed Solution

Define the 2 attributes qwpmin and qwpmax as lookup table.


Decision

Apply changes in the 302 and 457 FDIS July 2023 so that the standard is in line with IEC 61400-27-1:2020


Release Notes

Changes applied in both 302 and 457
- delete qwpmin and qwpmax for the class WindPlantQControlIEC
- add qwpmin and qwpmax in the enumeration WindLookupTableFunctionKind2

#1

Updated by Chavdar Ivanov 11 months ago

  • Status changed from New to Open
  • Author/Contact Info set to Chavdar Ivanov
  • Solution to be Applied To set to 18v05
  • Solution Version set to 18v05
  • Solution Applied By set to Chavdar Ivanov
  • Completion Date set to 07/01/2023
  • Breaking Change set to No
  • CIM Impacted Groups WG13 added
  • CIM Impacted Groups deleted (None)
#2

Updated by Chavdar Ivanov 11 months ago

  • Status changed from Open to Review
#3

Updated by Chavdar Ivanov 11 months ago

  • Status changed from Review to Closed
#4

Updated by Chavdar Ivanov 11 months ago

  • Solution Version changed from 18v05 to CIM18v05

Also available in: Atom PDF