Feature #586
Client application cannot connect to IED that are having issue with format of AP-Title
Added by Herbert Falk over 3 years ago.
Updated about 2 years ago.
Category:
Standard clarification required
TF Unique ID:
1340 # IOP_2019
WG10 Proposal:
Bruce to Create a tissue to update the schema to validate the format of AP-Title and others.Feb-2020: The tissue 1668 has been created, has been accepted and still under discussion the check that can be added.Jun-2020: There is an agreement on the tissue but it is still not green.
Discuss in Upcoming Meeting:
No
Description
Error found by ‘rise-clipse’ SCL File: IOP_2019_HV_v6_ed2.0.scd.
ERROR [RequiredAttributes] content shall be valid according to its type in P (line 1011)). The current value is 000 for type OSI-AP-Title.
As a consequence, the client application cannot connect to these IED.
This issue was detected when trying to connect to a relay. The value for AP-Title was not present in the ICD file, and a non-valid value was set by the SCT tool.
These values (000) are not correct for the application, although they are compliant with the SCL grammar (XSD schema)
- Subject changed from Error found by ‘rise-clipse’ SCL File: IOP_2019_HV_v6_ed2.0.scd.
ERROR [RequiredAttributes] content shall be valid a to Client application cannot connect to IED that are having issue with format of AP-Title
- Status changed from New to In Progress
- Standard(s) changed from 6 to IEC 61850-6
- WG10 Proposal changed from Bruce to Create a tissue to update the schema to validate the format of AP-Title and others.
Feb-2020: The tissue 1668 has been created, has been accepted and still under discussion the check that can be added.
Jun-2020: There is an agreement on the tissue but it is still not green. to Bruce to Create a tissue to update the schema to validate the format of AP-Title and others.Feb-2020: The tissue 1668 has been created, has been accepted and still under discussion the check that can be added.Jun-2020: There is an agreement on the tissue but it is still not green.
- Discuss in Upcoming Meeting set to No
- Discuss in Upcoming Meeting changed from No to Yes
- Status changed from In Progress to Closed
- Discuss in Upcoming Meeting changed from Yes to No
- To discuss in WG10 set to No
Related TISSUEs created #1734 and #1668.