An implementation do not allow BRCB resvTms to be written while rptEnable is True

Added by Herbert Falk over 3 years ago. Updated over 2 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Category:
Standard extension required
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
13
Source:
IOP_2017/22
TF Unique ID:
13 # IOP_2017/22
WG10 Proposal:

Already adressed

Estimated Completion:
(2019-06) No target date was set.
Discuss in Upcoming Meeting:
No
To discuss in WG10:
Short Proposal:

7-2 Editors have confirmed that this is correct behavior and has been clarified in Edition 2.1. No action is needed.

Standard(s):

IEC 61850-7-2

Needs More Information:
Assigned TF:

Description

An implementation did not allow BRCB resvTms to be written while rptEnable was true.
Both Ed2 and Ed2.1 require resvTms to be written as long as another client does not “owns” the control block.