TISSUE entered requesting SV subscriber testing

Added by Joel Greene about 2 years ago. Updated almost 2 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Start date:
02/25/2022
Due date:
% Done:

0%

Estimated time:

Description

We are a utility and we are in the middle of the engineering process for our upcoming full digital substations wherein we will be installing the IEDs which are capable of subscribing to Sampled Values. Now, the test certificates for Merging Units mention that they are tested for SV publishing test cases (e.g., Svp1, Svp2 etc.). So, we assumed that the protection and control IEDs which subscribe to SV streams should be tested for SV subscribing test cases (e.g., Svs1, Svs2 etc. as per 6.2.6.3 and 6.2.6.8.3 of IEC 61850-10), but we couldn’t find any IEDs which are tested for SV subscribing test cases (we've browsed the test certificates published on this website: http://www.ucaiug.org/org/TechnicalO/Testing/Lists/IEC61850Ed1ClientCertificates/AllItems.aspx )

As there are no test procedures available for SV subscribing test cases, we urge UCA and IEC TC 57 to issue the test procedures for SV Subscription as almost all the IED manufactures have their IEDs capable of subscribing to SV and utilities which are in the process of implementing full digital substations will be in a fix while engineering the systems as they will not be sure about the behavior of the protection and control IEDs subscribing to SV.
We also urge IED manufacturers to please mention the behavior of their IEDs (to the SV subscribing test cases e.g., Svs1, Svs2 etc.) in the PIXIT documents even though the test procedures for SV subscription are not defined.

Power Grid Corporation of India Limited

#1

Updated by Joel Greene almost 2 years ago

Per Bruce, these tests were added in 2021.

#2

Updated by Herbert Falk almost 2 years ago

  • Status changed from New to Closed

There have been several revisions to SV subscriber test cases.