CIM Issues #4049

SynchronousMachine attributes r and x are outdated Synchron

Added by Herbert Falk over 2 years ago.

Status:
Closed
Priority:
Normal
Author/Contact Info:
ENTSO-E 2012 IOP
Base Release:
61970cim16v10
Solution to be Applied To:
61970cim16v12
Solution Version:
CIM16
Solution Applied By:
KLH
Completion Date:
09/26/2012
CIM Keywords:
Breaking Change:
No
Breaking Change Description:
CIM Impacted Groups:
WG13
Requestor:
Standard(s):
Version:
Clause:
Sub-Clause:
Paragraph:
Table:
Originally Closed in Version:
CIM16
Origination Date:
07/22/2012
Origination ID:
13_111
Originally Assigned To:

Description

SynchronousMachine attributes r and x are outdated
SynchronousMachine.r and SynchronousMachine.x are present in the UML and in the profiles, but these attributes are not needed anymore. The reason is that additional attributes were added to complete the model of SynchronousMachine in respoect to short circuit and dynamics data exchanges.
(From Christoph Schmid) Synchronousmachine.r has been replaced by Synchronousmachine.equivalentResistance for the SHC calculation. For Dynamics Synchronousmachine.r has been replaced by RotatingMachine.statorResistance. (Chavdar please check in the ENTSO-E profile as I could not find this attribute in the html as attribute. It is only mentioned in the text). The attribute Synchronousmachine.x was required for Dynamics only and has been replaced by SynchronousMachineTimeConstantReactance.xDirectSync and SynchronousMachineTimeConstantReactance.xQuadSync


Proposed Solution

Remove attributes SynchronousMachine.r and x from 452 or from CIM UML.


Decision

(2012-08-22) Decided to check with Chavdar and remove attributes from CIM UML if not used by ENTSO-E.

(2012-09-05) WG 13 - Agreed to keep SynchronousMachine.r and to update the description with the text from SynchronousMachine.equivalentResistance, which will be removed. SynchronousMachine.x will also be removed.