Description

Terminal.connected attribute
documentation does not describe the usage with a bus-branch model.


Proposed Solution

Update documentation as follows
The connected status is related to a bus-branch model and the TopologicalNode-Terminal relation. True implies the Terminal is connected to the related TopologicalNode and false implies it is not.
In a bus-branch model the connected status is used to tell if equipment is disconnected without having to change the connectivity described by the TopologicalNode-Terminal relation. A valid case is that ConductingEquipment can be connected in one end and open in the other. In particular for an ACLineSegment where the charging can be significant


Decision

Updated as proposed