UCAIug Issue Tracking System: Issueshttps://redmine.ucaiug.org/https://redmine.ucaiug.org/favicon.ico?15861924492024-03-29T14:16:20ZUCAIug Issue Tracking System
Redmine IEC 61850 Certificate - IEC 61850 Certificate #6748 (Approved): IED1-E11D1 https://redmine.ucaiug.org/issues/67482024-03-29T14:16:20ZHerbert Falk
<p>Intelligent Electronic Device</p> IEC 61850 Certificate - IEC 61850 Certificate #6747 (Approved): WAGO 750-8212/0040-0001https://redmine.ucaiug.org/issues/67472024-03-29T14:06:13ZHerbert Falk
<p>Remote Terminal Unit</p> IEC 61850 Certificate - IEC 61850 Certificate #6746 (Approved): DW61850CLIENThttps://redmine.ucaiug.org/issues/67462024-03-29T14:00:26ZHerbert Falk
<p>SA-OPD (Substation Automation Operation Software)</p> WG16 Issues - CIM Issues #6745 (New): Need for consistent approach for Market Productshttps://redmine.ucaiug.org/issues/67452024-03-28T13:34:58ZScott Coe
<p>Market Products are not used consistently in the CIM because market products are not really consistent across markets...</p>
<p>Energy is the universal commodity; however, even when considering universal grid support products the names vary. In the North America, they call the load frequency control the Regulation product, but in Europe is is Secondary Reserve. Standby/emergency reserve products are more varied. Tertiary Reserve in Europe is split into Synchronous and Non-Synchronous Reserve in the North America. But in even in North America, there is inconsistent usage. PJM calls it Synchronized/Non-Synchronized, MISO and SPP have Spinning and Supplemental, NYISO/ISO-NE/CAISO use Spinning and Non-Spinning, and finally ERCOT has Responsive and Non-Spinning.</p>
<p>One of the oldest market enumerations, MarketProductType does not follow the typical format. We have: EN, RU, RD, SR, NR, RC, LFU, LFD, REG, RPU, CO2e, RMU, and RMD. Changing to Energy, RegulationUp, RegulationDown, SynchronousReserve or SpinningReserve, NonSynchronousReserve or NonSpinningReserve, ReliabibilityUnitCommitment, LoadFollowingUp, LoadFollowingDown, CarbonDioxideEquivalent, RegulationMileageUp, and RegulationMileageDown would break things.</p>
<p>Then we have a similar enumeration: ResourceCapacityType. RU, RD, SR, NR, MO, FO, RA, RMR which map to RegulationUp, RegulationDown, SynchronousReserve or SpinningReserve, NonSynchronousReserve or NonSpinningReserve, MustOffer, FlexibleOffer, ResourceAdequacy, and ReliabilityMustRun. Clearly a different use, but some of the concepts here overlap.</p>
<p>Finally, the most recent is ResourceCertificationKind which allows us to flag when a resource is certified to provide a service. Here the enumeration is properly formatted (all but one entry, that is) and again have a strong correlation to products: RegulationUp, RegulationDown, SpinningReserve, NonSpinningReserve, ReliabilityMustRun, BLACKSTART, DemandSideResponse, SynchronousCondenser, ReliabilityUnitCommittment, Energy, Capacity.</p> WG14 Part 3 Issues - CIM Issues #6744 (New): CrewStatusKind enumeration is missing values for dea...https://redmine.ucaiug.org/issues/67442024-03-26T16:56:48ZMartin Millermartin.miller@glires.com
<p>The current CrewStatusKind enumeration only contains entries for assignment of crews and the only value (fieldComplete) that represents the deassignment of a crew also represents the completion of work. It is missing any entries that represent the deassignment of a crew without completement of work.</p>
<p>At a minimum the enumeration needs an additional value to represent the concept of "Deassigned" which means that "the crew is no longer working on the outage in the field, without the outage being corrected". <br />Ideally, there would also be a second additional value to represent the concept of "Rejected" which means that "the crew has refused an assignment."</p> IEC 61850 Certificate - IEC 61850 Certificate #6742 (Approved): V321 Arc Flash Protection Systemhttps://redmine.ucaiug.org/issues/67422024-03-24T19:15:30ZHerbert FalkIEC 61850 Certificate - IEC 61850 Certificate #6741 (Approved): SA-G3000https://redmine.ucaiug.org/issues/67412024-03-24T19:09:32ZHerbert FalkIEC 61850 Certificate - IEC 61850 Certificate #6740 (Approved): ALARM ANNUNCIATOR MBAS 0600https://redmine.ucaiug.org/issues/67402024-03-24T18:50:11ZHerbert Falk
<p>MBAS 0600 Microprocessor/ Microcontroller Based Alarm Annunciator is designed to keep an alert and watchful eye on plant and processes. It is equipped with super bright LED facia windows , site selectable, programmed sequences as per ISA standard and optional customize sequences.</p> IEC 61850 User Feedback Task Force - Feature #6739 (New): How to deal with 'Beh' and 'Health' of ...https://redmine.ucaiug.org/issues/67392024-03-18T10:37:35ZMichael Haecker
<p>For site testing, users shall use the test mode to isolate devices/functions to prevent from flooding control centres with test data.</p>
<p>Whereas data marked "test" can be filtered out, changes of 'Beh' cannot be filtered out. When, for example, changing the active parameter set, the user will create data towards the control centre for LN instances which are activated/inactivated through this change.<br />[Part 7-4 Annex A: "Regardless of the status of LN.Beh, the quality test attribute of Mod, Beh and Health shall be q.test=false."]</p>
<p>In an automation system where a gateway is used to interface the control centre, this gateway could implement a feature to block the information flow of a device in test. Where a direct link via IEC 61850 is used, such blocking is not possible.</p> IEC 61850 User Feedback Task Force - Improvement #6738 (New): Amending TGSN LN class with setting...https://redmine.ucaiug.org/issues/67382024-03-18T10:14:44ZMichael Haecker
<p>The LN classes TCTR and TVTR inherit from 'InstrumentTransformerLN' some settings which can be used for adapting the output signal.</p>
<p>TGSN LN class is missing the settings for scaling, linerarization, wideing of a focussed range.</p> IEC 61850 User Feedback Task Force - Bug #6737 (New): Amending TGSN LN class with signal characte...https://redmine.ucaiug.org/issues/67372024-03-18T09:57:10ZMichael Haecker
<p>The model of a generic sensor does not provide characteristics about the analogue signal type which is used to receive the sensor value.</p>
<p>TC57/WG18 are proposing to amend the model with a setting to state the analogue signal type.</p> WG13 Issues - CIM Issues #6736 (New): Quality61850 Class does not match the definition of Quality...https://redmine.ucaiug.org/issues/67362024-03-12T21:05:03ZTom Berry
<p>CIM definition is missing Inconsistent, Inaccurate Boolean<br />IEC 61850 does not define Source = DEFAULTED</p>
<p>Encoding is now<br />/*
* Bit(s) Name Value<br /> 0-1 Validity Good 0 0<br /> Invalid 0 1<br /> Reserved 1 0<br /> Questionable 1 1<br /> 2 Overflow<br /> 3 OutofRange<br /> 4 BadReference<br /> 5 Oscillatory<br /> 6 Failure<br /> 7 OldData<br /> 8 Inconsistent<br /> 9 Inaccurate<br /> 10 Source Process 0<br /> Substituted 1<br /> 11 Test<br /> 12 OperatorBlocked<br /> */</p> WG16 Issues - CIM Issues #6735 (New): new disclaimer note on every Inf* UML diagram indicating to...https://redmine.ucaiug.org/issues/67352024-03-11T19:54:31ZBecky Iverson
<p>We need to indicate the usage of Inf in a more explicit way to avoid confusions.</p> WG16 Issues - CIM Issues #6734 (New): Review use/inheritance of Document by UCA TF 16 classes, pr...https://redmine.ucaiug.org/issues/67342024-03-11T14:58:20ZBecky Iverson
<p>UTF 14 is reviewing all classes that are inheriting from Document and has request UTF 16 to review the use of Document class.</p> IEC 61850 Certificate - IEC 61850 Certificate #6733 (Approved): ETLID1000https://redmine.ucaiug.org/issues/67332024-03-11T13:38:57ZHerbert Falk