Redmine 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6699 (New): Behavior of a function while being dynamica...https://redmine.ucaiug.org/issues/66992024-02-07T10:55:45ZKeith Gray
<p>LN.blk is active.<br />What happens with the functionality such as timers and outputs?</p> 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6698 (New): Integrate work from AHTF Control Between Fu...https://redmine.ucaiug.org/issues/66982024-02-07T08:08:31ZKeith Gray
<p>Collect the work created by this AHTF and integrate it into 7-5 and 7-500. We need to locate the latest draft of the document, review that draft, and determine how to integrate it with our documents.</p> 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6555 (New): Behaviour of output contacts when LN is in ...https://redmine.ucaiug.org/issues/65552023-10-26T07:52:10ZKeith Gray61850-7-5 and 61850-7-500 - IEC61850-7-5 #6554 (Waiting for Release): SwModKey seems to overwrite...https://redmine.ucaiug.org/issues/65542023-10-26T07:51:39ZKeith Gray
<p>This was assigned to 7-5/7-500 TF during the 7-5/7-500 meeting in Kista, Sweden on 2023/10/25.</p> 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6537 (New): Harmonizing expressions in 7-500 Ed.1https://redmine.ucaiug.org/issues/65372023-10-06T13:13:34ZMichael Haecker
<p>In IEC/TR 61850-7-500 Ed.1<br />the term</p>
<pre><code>"BIED" (Breaker IED means process near circuit breaker controller same as CBC)<br />is used in a mix with the term<br /> "CBC" (Process near circuit breaker controller IED according to IEC 62271-3 instead of BIED (breaker IED))</code></pre>
<p>and the term</p>
<pre><code>"SIED" (Switch IED means process near disconnector/earthing switch controller same as DCC and/or ESC)<br />is used in a mix with the terms<br /> "DCC" (Process near disconnector controller IED according to IEC 62271-3<br />instead of SIED (switch IED)) and<br /> "ESC" (Process near earthing switch controller IED according to IEC 62271-3 instead of SIED (switch IED)).</code></pre>
<p>In drawings only one of the parallel terms is used.</p>
<p>This is to propose to use only one of the parallel terms and to put a general note referring to the other one.</p> 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6500 (In Progress): Parameters to enforce the checking ...https://redmine.ucaiug.org/issues/65002023-08-02T16:14:35ZMichael Haecker
<p>Enhancement of the datamodel with two new setting parameters 'EnfItl' and 'EnfSyn'.<br />The concept was already developed in TF "Control between functions".</p>
<p>cross reference to <a class="issue tracker-13 status-2 priority-2 priority-default" title="IEC61850-7-5: Explanation text on the application of check conditions (In Progress)" href="https://redmine.ucaiug.org/issues/6499">#6499</a></p>
<p>Update of table "Dependance of checking interlocking conditions on the control service parameters and on the server operational configuration"</p> 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6499 (In Progress): Explanation text on the application...https://redmine.ucaiug.org/issues/64992023-08-02T16:08:20ZMichael Haecker
<p>A chapter to be added to explain the application of check conditions.</p>
<p>cross reference to <a class="issue tracker-13 status-24 priority-2 priority-default" title="IEC61850-7-5: Explanation text on the usage of SwModKey (Waiting for Release)" href="https://redmine.ucaiug.org/issues/6498">#6498</a></p>
<p>Include a table to show the dependance of checking interlocking conditions on the control service parameters and on the server operational configuration</p> 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6498 (Waiting for Release): Explanation text on the usa...https://redmine.ucaiug.org/issues/64982023-08-02T15:59:10ZMichael Haecker
<p>A chapter to be added to explain the usage of SwModKey.</p>
<p>cross reference to <a class="issue tracker-13 status-2 priority-2 priority-default overdue" title="IEC61850-7-5: Clarifications on the local/remote concept 6/8 (In Progress)" href="https://redmine.ucaiug.org/issues/6392">#6392</a></p>
<p>To be clarified whether there is a dependency (out of the datamodel hierarchy) IHMI.SwModKey > LD/LLN0.SwModKey > CSWI.SwModKey</p> 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6395 (Waiting for Release): Figure 15 SelOpn and SelCls...https://redmine.ucaiug.org/issues/63952023-06-14T14:26:03ZKeith Gray
<p>I found an inconsistency in SelOpn and SelCls definitions between IEC 61850-7-500 Ed2 and 61850-7-4 Ed2.1. Can we discuss this during today’s meeting if time permits?</p>
<p>Figure 15 in 61850-7-500 shows SelOpn and SelCls with per-phase data attributes (as if it were an ACT). However, 61850-7-4 Ed2.1 defines SelOpn and SelCls as SPS. Even for single-phase control, the selection has to be per-switch. I believe this diagram needs to be updated.</p>
<p>Thanks,</p>
<p>Priyanka Nadkar<br />Development Lead Engineer<br />Research and Development<br />Schweitzer Engineering Laboratories<br />901 Center Park Drive, Charlotte, NC 28217 USA | Office: (704)-504-6804</p> 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6393 (In Progress): Clarifications on the local/remote ...https://redmine.ucaiug.org/issues/63932023-06-14T13:22:48ZVladan Cvejic
<p>Add a statement in the description text of 'MltLev' that this setting effects all contained LN instances of that LD.<br />Is the dependency of 'MltLev' limited to contained LN instances of that LD or, in the case of nested LD, including also subordinate levels?</p> 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6392 (In Progress): Clarifications on the local/remote ...https://redmine.ucaiug.org/issues/63922023-06-14T13:22:18ZVladan Cvejic
<p>Add a statement in the description text of 'SwModKey' that this setting effects all contained CSWI LN instances of that LD.<br />Is the dependency of 'SwModKey' limited to contained CSWI LN instances of that LD or, in the case of nested LD, including also subordinate levels?</p> 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6391 (In Progress): Clarifications on the local/remote ...https://redmine.ucaiug.org/issues/63912023-06-14T13:21:58ZVladan Cvejic
<p>Add a statement about the dependency of 'LN.Loc' contained in LD from LD/LLN0.Loc (and LocSta, as applicable). Is this dependency limited to contained LN instances of that LD or, in the case of nested LD, including also subordinate levels? (see Tissue 1778)</p> 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6390 (In Progress): Clarifications on the local/remote ...https://redmine.ucaiug.org/issues/63902023-06-14T13:21:41ZVladan Cvejic
<p>Add a statement about the dependency of LD contained LN.LocSta from LD/LLN0.LocSta . Part 7-1 clause 6.4.2.1, Figure 14 states "for complete LD". Is the statement in the figure applicable for 'MtlLev' only or for both 'MltLev' and 'LocSta'?</p> 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6378 (In Progress): Clarifications on the local/remote ...https://redmine.ucaiug.org/issues/63782023-06-14T13:17:34ZVladan Cvejic
<p>Add a statement about the intention of the L/R concept. Specify whether the L/R concept is applicable for the control of switchgear exclusively, not for controls in general. Note the saying "if the LN class includes 'Loc' and 'LocSta' data, then this LN class falls under L/R". Applicable for
{ANCR, ARIS, ATCC, AVCO, CCGR, CSWI, CSYN, FSPT, GAPC, GGIO, IHMI, ITCI, KFAN, KFIL, KPMP, KVLV, LLN0, RSYN, XCBR, XSWI, YEFN, YLTC, YPSH, ZRRC}<br />Within such an LN class, clarify/list the controllable objects which fall under the L/R concept, e.g. 'XCBR.Pos' - yes, 'XCBR.OpCntRs' - no</p> 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6376 (New): LN PDIF – setting for nominal currenthttps://redmine.ucaiug.org/issues/63762023-06-14T13:16:51ZVladan Cvejic
<p>LN PDIF contains DO LoSet and HiSet which represent Low (resp High) operate value setting [%] relative to the nominal current. <br />As the nominal current is not a setting in PDIF, how could a user set the value of the threshold for minimal (resp. maximal) differential current ?</p>
<p>In practice, the base current for PDIF is often the highest primary nominal current of the associated TC.</p>