Redmine IEC 61850 User Feedback Task Force - Feature #6739 (New): How to deal with 'Beh' and 'Health' of ...https://redmine.ucaiug.org/issues/67392024-03-18T10:37:35ZMichael Haecker
<p>For site testing, users shall use the test mode to isolate devices/functions to prevent from flooding control centres with test data.</p>
<p>Whereas data marked "test" can be filtered out, changes of 'Beh' cannot be filtered out. When, for example, changing the active parameter set, the user will create data towards the control centre for LN instances which are activated/inactivated through this change.<br />[Part 7-4 Annex A: "Regardless of the status of LN.Beh, the quality test attribute of Mod, Beh and Health shall be q.test=false."]</p>
<p>In an automation system where a gateway is used to interface the control centre, this gateway could implement a feature to block the information flow of a device in test. Where a direct link via IEC 61850 is used, such blocking is not possible.</p> IEC 61850 User Feedback Task Force - Bug #6737 (New): Amending TGSN LN class with signal characte...https://redmine.ucaiug.org/issues/67372024-03-18T09:57:10ZMichael Haecker
<p>The model of a generic sensor does not provide characteristics about the analogue signal type which is used to receive the sensor value.</p>
<p>TC57/WG18 are proposing to amend the model with a setting to state the analogue signal type.</p> IEC 61850 TPWG - Bug #6622 (Rejected): Test case Ttf1 (mustUnderstand) for the ICT conformance te...https://redmine.ucaiug.org/issues/66222023-12-06T16:41:38ZKaren Wyszczelski
<p>The test should be modified to test three scenarios.</p>
<p>An element has a mustUnderstand in the communication section of the IED being configured, but the IED being configured does not support it.<br /> The ICT should reject the configuration of the IED and provide an error message.</p>
<p>An element has a mustUnderstand outside the scope of the IED being configured.<br /> The ICT should import the file.</p>
<p>An element has a mustUnderstand element that is in another device but the SCD is configured for use in the IED being configured.<br /> The ICT should reject the configuration of the IED and provide an error message.</p>
<p>Currently mustUnderstand is only used for R-GOOSE and R-SV.</p> IEC 61850 User Feedback Task Force - Bug #6596 (Resolved): Simulation Mode with Centralized Prote...https://redmine.ucaiug.org/issues/65962023-11-12T10:40:07ZDustin Tessier dtessier@tescoautomation.com
<p>During a recent vPAC Alliance meeting the topic of LPHD.Sim was discussed and how it would not support a centralized protection scheme, which forces the entire physical device (centralized computing platform) to be placed into simulation mode. Ideally the simulation modes could be applied to LDs (similar to test mode via LLN0), however this would create backwards compatibility issues. The other option is to not use simulation mode, and use the LN's InRef's tstEna/setTstRef data objects to dynamically subscribe to the test set.</p> IEC 61850 User Feedback Task Force - Bug #6263 (Resolved): GOOSE MinTime / Max Time - Probable di...https://redmine.ucaiug.org/issues/62632023-02-14T11:24:58ZAbhilash Appukuttanabhilash.appukuttan1@ge.com
<p>In Part 6, the MinTime and MaxTime is expressed as 'Decimal'</p>
<p><xs:complexType name="tGSE"><br /><xs:complexContent><br /><xs:extension base="tControlBlock"><br /><xs:sequence><br /><xs:element name="MinTime" type="tDurationInMilliSec" minOccurs="0"/><br /><xs:element name="MaxTime" type="tDurationInMilliSec" minOccurs="0"/><br /></xs:sequence><br /></xs:extension><br /></xs:complexContent><br /></xs:complexType><br />---<br /><xs:complexType name="tDurationInMilliSec"><br /><xs:simpleContent><br /><xs:extension base="xs:decimal"><br /><xs:attribute name="unit" type="tSIUnitEnum" use="optional" fixed="s"/><br /><xs:attribute name="multiplier" type="tUnitMultiplierEnum" use="optional" fixed="m"/><br /></xs:extension><br /></xs:simpleContent><br /></xs:complexType></p>
<p>However, in 8-1, the MinTime and MaxTime is an Unsigned32 / INT32U</p>
<p>MinTime Unsigned32 r o INT32U – As specified in the SCD<br />file for the GoCB, See 1<br />MaxTime Unsigned32 r o INT32U – As specified in the SCD<br />file for the GoCB. See 1</p>
<p>What shall the ICT process the values as? Input as Decimal and then pass it as Integer to the application?</p>
<p>Or does it makes sense to change the -6 to have these values as Integer?</p>
<p>If you look at Table 45 in -6, it does point to that way.</p>
<p>INT8, INT16, INT24, INT32,<br />INT64<br />INT8U, INT16U, INT32U</p>
<p>integer</p>
<p>An integer number, no decimal fraction (99999)</p> IEC 61850 User Feedback Task Force - Bug #6256 (Resolved): IEC 61850-7-4 list of abbreviationshttps://redmine.ucaiug.org/issues/62562023-02-09T19:27:57ZMichael Haecker
<p>Clause 4.2 / Table 1 of Part 7-4 lists the abbreviations used in data object names.</p>
<p>In this list entries exist which refer to (parts of) former DO names. When removing DO / changing DO names of former versions, model managers of other Parts do not inform the Part 7-4 editor to delete the entries from the list.</p>
<p>The standard (and the web access datamodel) expose abbreviations which are not used any more.</p>
<p>Example: string "Ia" : 16 entries</p> IEC 61850 User Feedback Task Force - Bug #6226 (Resolved): In the downgrading rules from ed 2.1 t...https://redmine.ucaiug.org/issues/62262023-01-17T09:05:39ZAurelie Dehouck
<p>61850-6 ed2.1 mention in I.4.2.4 "New CDC":</p>
<p>"The CDC ORS has been added to the list of the allowed CDCs. DOType whose CDC=ORS shall be excluded from the export to an 2007B environment. This includes also DO instances using this type."</p>
<p>But other CDCs were also added (cf tPredefinedCDCEnum, or 7-3): CST, VSD and TCS<br />Why shouldn't they be excluded also ?</p> IEC 61850 User Feedback Task Force - Bug #6175 (In Progress): SCL SICS requires SNTP even with 2....https://redmine.ucaiug.org/issues/61752022-11-06T14:40:52ZHerbert Falk
<p>See attached problem report.</p> IEC 61850 User Feedback Task Force - Bug #3101 (Resolved): IEC61850.Tissue #1755 Event driven sch...https://redmine.ucaiug.org/issues/31012021-08-10T09:59:06ZHenry Dawidczak
<p>Part 7-4, page 169/482, clause 6.6.9 table 70:<br />The possibility to stop an event driven schedule by another event is missing.<br />Defining an additional DO would allow that starting and stopping a event driven schedule could be represented by two independent trigger events.</p>
<p>Example: A local DO event may represent a communication failure. The transition (False to True) of the DO referenced by InSyn could indicate that the communication has a failure (which should start a specific schedule). The transition (False to True) of the DO referenced by (new) DO InSynStop could indicate that the communication is again operating properly (which should cause the schedule to stop immediately).</p> IEC 61850 User Feedback Task Force - Feature #631 (Triage): Evolution of LN PSCH to build switchi...https://redmine.ucaiug.org/issues/6312021-02-16T08:19:53ZCarlos Rodriguez del Castillo
<p>LN PSCH "is used to model the logic scheme for line protection function co-ordination.The protection scheme ('PSCH.Op') allows the exchange of the operate outputs of different protection functions ('Pxxx.Op') and conditions for line protection schemes. It aggregate the Pxxx.Op of the system to build the trip information." <br />Same mechanisms should be provide to build the switching on / distance switching on information.<br />Needed for some PACS functions.</p> IEC 61850 User Feedback Task Force - Feature #623 (In Progress): New LN of group L (as "LPLE") re...https://redmine.ucaiug.org/issues/6232021-02-16T07:53:49ZCarlos Rodriguez del Castillo
<p>Need to have a new LN of group L (as "LPLE") representing a group of LED of the IED front panel.<br />The LN representing the interfaces are used for the monitoring of these I/O and to map the physical terminal to the corresponding DO.<br />Helpful for maintenance and exploitation of the system.</p> IEC 61850 User Feedback Task Force - Feature #619 (Resolved): New LN of group L (as "LTED") to re...https://redmine.ucaiug.org/issues/6192021-02-16T07:38:40ZCarlos Rodriguez del Castillo
<p>Details:<br />Some functions need to know the current topology of the substation.<br />For doing that, <br />- 1 LN LTED is instanciated for each feeder connected to the busbar and for each busbar segment.<br />- ElNodeRef indicates the reference number of the electrical node of the busbar to which the LN is associated, calculated on the base of its actual topology (disconnector and circuit breaker position). <br />- ElNodeNum indicates the total number of electrical nodes into which a busbar is splitted on the base of its actual topology (disconnector and circuit breaker position). <br />- ElNodeVTRef is used by the LD publishing voltage information (SV or PhV). Only one LD can adopt the number of the Electrical Node. This LD published the busbar voltage reference for corresponding electrical node, indicating if this voltage is to be used as voltage reference for an Electrical Node. If not, its value is set to zero.</p>
<p>Argument: Needed for some PACS functions.</p> IEC 61850 User Feedback Task Force - Bug #611 (In Progress): Need a new DO (ENUM) to identify the...https://redmine.ucaiug.org/issues/6112021-02-15T19:01:57ZCarlos Rodriguez del Castillo
<p>This ENUM will allow to identify the type of the distant center (104, IEC61850), in case several centers are connected to the substation.<br />Helpful for maintenance and exploitation of the system.</p> IEC 61850 User Feedback Task Force - Feature #599 (Resolved): ICD files do not match requirements...https://redmine.ucaiug.org/issues/5992021-02-03T20:07:41ZHerbert Falk
<p>ICD files did not match requirements.</p>
<p>The icd file delivered for the initial configuration had a generic (out of the box) data model. The SCT was not able to map all required information into the IED – multiple iterations were required until the ICD file was finally reflecting the requirements.</p>
<p>Sometimes, that was just the data model as such (i.e., the control of a switch (CSWI.Pos) was preconfigured as status-only and could not be changed by the tool as the data model did not provide the structure for control) – the system design engineer had to communicate verbally with the IED what is needed and got a new file back with the modifications in the IED tool.</p>
<p>Sometimes, GOOSE messages could not be configured. Again – through verbal interaction, the system design engineer told the IED design engineer what he needs as signals and the IED engineer configured the dataset for the GOOSE control block accordingly, such that it could then support the requirements. This required additional iterations.</p>
<p>The process needs to be clarified! According the standard, an icd file is a – if needed pre-configured – file that matches the requirements from the substation. The less flexibility an IED tool provides regarding configurability by the system tool, the more preconfiguration is needed. That requires the essential design work to be done in multiple tools.</p>
<p>To avoid this, the standard should enforce flexibility of the IED tools with regard to engineering capabilities through the system tool.</p> IEC 61850 User Feedback Task Force - Bug #439 (Resolved): How to add utility process name to DOshttps://redmine.ucaiug.org/issues/4392021-02-03T20:07:32ZHerbert Falk
<p>Currently SCL has poor support for handling gateway/RTU-funktions where signal names are translated for remote communication. The specified sigal has a utility process name independent of used protcol. E.g. "start of distance protection". This needs to be associated with its IEC 61850 implementation (xxPDIS1.Str.general, xxPDIS2.Str.general etc.). The 80-1 part describes how 104 addresses can be added to SCL but also other utility fields are important to be able to include in SCL for specification and documentation purposes. Desired solution by Vattenfall is to have vendors use DA description to add utility process name.</p>