UCAIug Issue Tracking System: Issueshttps://redmine.ucaiug.org/https://redmine.ucaiug.org/favicon.ico?15861924492023-06-15T06:50:19ZUCAIug Issue Tracking System
Redmine IEC 61850 TPWG - Issues #6396 (Closed): Review SV test procedureshttps://redmine.ucaiug.org/issues/63962023-06-15T06:50:19ZJoel Greenejoel@sisconet.com
<p>Do we have correct coverage for current editions?</p>
<p>Do we need to address TC38 for 61869 testing?</p> Server - Issues #6142 (Closed): TemplatePics_Ed1Ed2Ed2p1_Excel_rev3p1 contains wrong comment for T2https://redmine.ucaiug.org/issues/61422022-09-27T12:02:58Zchristian zehnder
<p>Assume its a typo in the latest PICS template on ACSI Service tab for T2:<br />T3 (µs) (<= 25 µs), 15 <= T3 < 18<br />T4 (µs) (<= 25 µs), 18 <= T3 < 19</p>
<p>According 7-2:2010 and 2020 T4 is 4us not 25:</p>
<p>T4 (µs) (<= 4 µs), 18 <= T3 < 19</p>